Governor's Office Emergency Services |
TIME: 1226 |
|
Cal OES - 24-2128 NRC - |
1. NAME: | 2. AGENCY: | 3. PHONE#: | 4. Ext: | 5. PAG/CELL: |
![]() | Grifols Diagnostic Solutions | ![]() | ![]() | ![]() |
1. NAME: | 2. AGENCY: | 3. PHONE#: | 4. Ext: | 5. PAG/CELL: |
![]() | ![]() | ![]() | ![]() |
2. a. SUBSTANCE: | b.QTY:>=< | Amount | Measure | c. TYPE: | d. OTHER: | e. PIPELINE | f. VESSEL >= 300 Tons |
1. Mix Solvent Waste | = | 10 | Gal(s) | CHEMICAL, VAPOR | No | No | |
2. | = | No | No | ||||
3. | = | No | No |
g. DESCRIPTION: | Per the Reporting Party : Incident occurred inside a biotech/manufacturing facility. Due to a faulty sensor, a sealed waste collection drum overflowed 10 gallons of mix solvent waste into a secondary containment vessel that did not have a lid. From the secondary containment vessel vapor escaped and released into the room atmosphere, into a ventilation system and then outside the building into the atmosphere. The material that released in vapor form was a combination of acetonitrile (40% to 60%), dichloromethane (20%-30%), dichloroacetic acid (5%-10%), and pyridine (5%-10%). This occurred inside a "H3" rated room in the facility. The vapor release began around 1930 on 4/9/2024 and was stopped at 2015 on 4/9/2024. The material released into the atmosphere is unrecoverable. A contractor responded to pump the waste out of the overflow container in to a new drum. | ||
![]() | ![]() | ![]() | ![]() |
h. STOPPAGE/CONTAINMENT: | i. WATER INVOLVED: | j. WATERWAY: | k. DRINKING WATER IMPACTED |
Stopped, Contained | No | N/A | No |
![]() | ![]() | ![]() | |
l. MARITIME VESSEL No | ![]() | m. KNOWN IMPACT Unknown | ![]() |
![]() | ![]() | ![]() | ![]() |
3. a. INCIDENT LOCATION: 10808 Willow Court | |||
b. CITY: | c. COUNTY: | d. ZIP: | ![]() |
![]() | ![]() | ![]() | ![]() |
San Diego | San Diego County | 92127 | SAN DIEGO COUNTY APCD |
4. INCIDENT DESCRIPTION: | |||
a. DATE: | b. TIME (Military): | c. SITE: | d. REPORTED CAUSE |
04/09/2024 | 1930 | Other Description for Other : Biotech / manufacturing facility | Mechanical |
![]() | ![]() | ![]() | |
![]() | ![]() | ![]() | ![]() |
e. INJURIES | f. FATALITY | g. EVACUATION | h. CLEANUP BY: |
No | No | No | Contractor |
6. NOTIFICATION INFORMATION: | ||
a. ON SCENE: | b. OTHER ON SCENE: | c. OTHER NOTIFIED: |
CUPA |
d. ADMIN. AGENCY: San Diego County Health Services Department | ![]() | e. SEC. AGENCY: |
f. ADDITIONAL COUNTY: | ![]() | g. ADMIN. AGENCY: |
h. NOTIFICATION LIST: | ![]() | ![]() |
Cal GEM: | RWQCB Unit: | 9 |
Cal OES Region: | ![]() | |
![]() | ||
![]() | ![]() | ![]() |
Photo Attachment: | ![]() |